Office and business centre

Office building (business centre) for approximately 400 employees: a 5-storey office block, an adjoining conference hall and canteen block, an entrance plaza, surface and underground car parks, and a fire access road around the building. Click an element in the model to open the code requirements that apply to it.

The sample model is a scheme. Sizes and distances follow the requirements below, but it is not a finished design.

Sample model figures

Staff (sample)
~400 people
Floors
office block 5 (18 m), conference hall and canteen block 1
Total floor area (based on external dimensions)
4,366 m² (office block 5 × 810, block 316)
Parking spaces (required)
437 — 1 per 10 m² (Table 29)
Parking spaces (in the model)
487: 171 above ground, ~316 underground
Spaces for people with disabilities (10%)
49: 18 above ground, 31 underground
Electric vehicle spaces (5%)
25: 9 above ground, 16 underground
Red line to building
28 m
Fire access road
width 4.2 m, 6–8 m from the walls
Car parks to building
15 m (51–100 spaces), 25 m
Underground ramp to windows
15.6 m

Indicators are calculated from the dimensions of the sample model.

Requirements to consider in design

65 key requirements. The short summary is by BIMFAB; “Code text” is a verbatim quote from the code. Always check the full, current text in the code itself.

Location and site

  1. Site area per employee: for government administration bodies in a 3–5-storey building — 44–19 m², for design organisations in 2–5-storey buildings — 30–15 m².

    ШНҚ 2.07.01-23, 50-жадвал

    Code text
    Ер участкалари майдони | Давлат бошқаруви муассаса ва ташкилотлари, объект (жумладан туман ва шаҳар ҳокимликлари) | 44 — 19 m^{2} — 3 — 5 қаватли бинода | Лойиҳа ташкилотлари | 30 — 15 m^{2} — 2-5 қаватли биноларда

Site plan

  1. For administrative buildings, at least 1 parking space in the car park is required for every 10 m² of building area.

    ШНҚ 2.07.01-23, 29-жадвал

    Code text
    Ҳисоб бирлигига машина-жойлари сони (камида) | Маъмурий бинолар | бинонинг ҳар 10 m^{2} майдони | 1 та
  2. Car park site area per parking space, minimum: open — 25 m² (with landscaping — 35 m²), 2-storey — 20, 3-storey — 14, 4-storey — 12, 5-storey — 10 m².

    ШНҚ 2.07.01-23, 413-банд

    Code text
    бир машина-жой учун камида, m^{2}: 2-қаватли автотураргоҳлар — 20; 3-қаватли автотураргоҳлар — 14; 4-қаватли автотураргоҳлар — 12; 5-қаватли автотураргоҳлар — 10; очиқ атотураргоҳлар — 25; кўкаламзорларни ҳисобга олган ҳолда очиқ атотураргоҳлар учун — 35.
  3. Car park entrances and exits must be located at least 50 m from intersections of arterial streets, 20 m from local streets and 5 m from public transport stops.

    ШНҚ 2.07.01-23, 414-банд

    Code text
    Автотураргоҳларнинг кириш-чиқиш жойлари магистрал кўчалар чорраҳаларидан камида 50 m, маҳаллий аҳамиятидаги кўчалардан 20 m, жамоат транспорти бекатларидан 5 m масофада бўлиши керак.
  4. Entrances and exits of underground car parks must be at least 15 m away from the windows of residential and public buildings and from the grounds of educational and healthcare institutions.

    ШНҚ 2.07.01-23, 415-банд

    Code text
    Ерости автотураргоҳларининг кириш-чиқиш жойлари турар жой ва жамоат бинолари деразаларидан, шунингдек таълим ва даволаш муассасалари ҳудудларидан камида 15 m узоқликда бўлиши керак.
  5. Distance from open and above-ground car parks to the windows of public buildings: up to 50 cars — 10 m, 51–100 — 15 m, 101–300 and over 300 — 25 m.

    ШНҚ 2.07.01-23, 30-жадвал

    Code text
    Масофа, m | Ерусти, ерусти-ерости ҳамда очиқ автотураргоҳлар, енгил автомобиллар сони | 10 гача | 11 — 50 | 51 — 100 | 101 — 300 | 300 дан зиёд | Жамоат бинолари | 10 | 10 | 15 | 25 | 25
  6. In car parks of shopping and business centres, at least 5% of parking spaces (at least one space) must be allocated for charging electric and hybrid vehicles.

    ШНҚ 2.07.01-23, 412-банд

    Code text
    Бунда, мазкур инфратузилма объектлари автотураргоҳларидаги машина жойларининг камида 5 фоизи (лекин битта жойдан кам бўлмаган ҳолда) электромобиллар ва гибрид автомобилларни қувватлантириш учун ажратилиши керак.
  7. Bicycle parking must be located near the entrances to public and administrative buildings, in public green areas and in car parks.

    ШНҚ 2.07.01-23, 408-банд

    Code text
    Велосипедларни сақлаш учун кўп квартирали уй-жойлар, жамоат, маъмурий, ижтимоий ва ишлаб чиқариш биноларига кириш жойлари яқинида, умумий фойдаланишдаги кўкаламзорлар ҳудудларида, шунингдек автотураргоҳларда велосипед тураргоҳлари жойлаштирилиши керак.
  8. Driveways and footpaths shall be located at least 5 m from the walls of residential and public buildings.

    ШНҚ 2.07.01-23, 337-банд

    Code text
    Ўтиш йўллари ва пиёдалар йўлаклари турар жой ва жамоат бинолари деворларидан камида 5 m узоқликда жойлаштирилиши лозим.
  9. Local streets in public-business and commercial zones: design speed 50 km/h, lane width 3.0–3.5 m, number of lanes 2–4, minimum footway width 2.0 m.

    ШНҚ 2.07.01-23, 20-жадвал

    Code text
    Ҳаракатнинг ҳисобланган тезлиги, km/h | Тасма кенглиги, m | Тасмалар сони (жами икки йўналишда) | Пиёдалар йўлагининг энг кичик кенглиги, m | ижтимоий-амалий ва савдо зоналардаги кўчалар | 50 | 3,0-3,5 | 2 — 4 | 2,0
  10. On the sites of free-standing buildings and structures, an area of not less than 30% of the building footprint must be landscaped (planted with trees).

    ШНҚ 2.07.01-23, 474-банд

    Code text
    Алоҳида турувчи бино ва иншоотлар ёки уларнинг мажмуалари ҳудудлари бино (иншоот)ларнинг қурилиш майдонининг 30 фоизидан кам бўлмаган майдони кўкаламзорлаштирилган (дарахт экилган) бўлиши лозим.
  11. In Tashkent, when non-residential buildings (other than industrial) with a total volume of 300 m³ or more are designed, at least one tree and two shrubs must be planted for every 100 m² of the building's total floor area.

    ШНҚ 2.07.01-23, 474-банд

    Code text
    шунингдек умумий ҳажми 300 м^{3} ва ундан ортиқ бўлган нотурар жой бинолари (саноат объектлари бундан мустасно) лойиҳалаштирилаётганда бино умумий майдонининг ҳар 100 квадрат метрига камида битта дарахт ва иккита бута кўчатлари экилиши лозим.
  12. Distance from the tree trunk axis to the building's external wall — 5.0 m, shrub — 1.5 m; to the edge of a pavement or garden path: tree — 0.7 m, shrub — 0.5 m.

    ШНҚ 2.07.01-23, 35-жадвал

    Code text
    Бино, иншоот, объектдан ўққача масофалар, m | дарахт пояси | бута пояси | Бино ва иншоотнинг ташқи девори | 5,0 | 1,5 | Тротуар ва боғ йўлкаси чети | 0,7 | 0,5
  13. Where the building has no refuse chute, a refuse collection room must be provided on the ground floor, and a dedicated hard-surfaced area for waste containers on the building site.

    ШНҚ 2.08.02-23, 143-банд

    Code text
    Бинода чиқинди тушириш қувури бўлмаганда биринчи қаватда чиқинди ташлаш камераси, бино участкасида чиқиндиларни тўпловчи контейнер учун қаттиқ қопламали махсус майдонча лойиҳаланиши лозим.

Building: layout and massing

  1. Administrative buildings must not exceed 16 storeys; exceeding 16 storeys is permitted subject to a special feasibility study and technical specifications being developed.

    ШНҚ 2.08.04-22, 6-банд

    Code text
    Бунда, маъмурий биноларнинг қаватлари сони 16 қаватдан ошмаслиги лозим. Қаватлар сонини 16 қаватдан оширишга махсус техник-иқтисодий асослар ва техник шартлар ишлаб чиқиш билан йўл қўйилади.
  2. The floor-to-ceiling height of rooms in public buildings must be at least 3.0 m.

    ШНҚ 2.08.02-23, 8-банд

    Code text
    Жамоат бинолари хоналарининг баландлиги полдан шифтгача 3,0 m дан кам бўлмаслиги зарур.
  3. Workrooms of administrative bodies, insurance and financial organisations, design organisations and research institutes are designed at no less than 6 m² per staff member, and at 4–5 m² per employee in multi-occupancy workrooms.

    ШНҚ 2.08.02-23, 679-банд

    Code text
    Бошқариш муассасалари, вазирликлар, суғурта ва молия ташкилотлари, лойиҳа ҳамда ИТИ ходимлари учун маъмурий вазифадаги хоналар, ишчи хоналар битта штат ходимига камида 6 m² майдон тўғри келишини ҳисобга олган ҳолда лойиҳаланиши, бунда кўп ўринли ишчи хоналарида бир ходимга тўғри келадиган майдон 4-5 m² бўлиши керак.
  4. Lobbies without a cloakroom must be designed at no less than 0.17 m² per person, and lobbies with a cloakroom at no less than 0.25 m² per person.

    ШНҚ 2.08.02-23, 684-банд

    Code text
    Гардеробсиз вестибюллар бир нафар кишига камида 0,17 m², гардеробли вестибюллар бир нафар кишига камида 0,25 m² юза тўғри келишини ҳисобга олган ҳолда лойиҳаланиши лозим.
  5. Staff toilets: 1 WC per 20–25 women and 1 personal hygiene cubicle per 70–75 women; 1 WC and 1 urinal per 30 men.

    ШНҚ 2.08.02-23, 687-банд

    Code text
    Ходимлар учун санитария узелларини қуйидагиларни ҳисобга олган ҳолда лойиҳаланиши лозим: 20 — 25 нафар аёлга 1 та унитаз ва 70 — 75 нафар аёлга 1 та шахсий гигиена кабинети; 30 нафар эркакка 1 та унитаз ва 1 та писсуар тўғри келишини.
  6. Toilets may be located on alternate floors, but their distance from workrooms must not exceed 75 m.

    ШНҚ 2.08.02-23, 688-банд

    Code text
    Санитария узелларини (эркаклар, аёллар учун) қават ташлаб жойлаштиришга йўл қўйилиши, лекин уларнинг иш хоналаридан узоқлиги 75 m дан ошмаслиги зарур.
  7. Conference hall area per seat: up to 100 seats (around a table) — 1.3–2 m²; in a hall with 100–150 seats — 1–1.1 m² (with lectern desks — 1.25 m²); in a hall with more than 150 seats — 0.9–1.0 m².

    ШНҚ 2.08.02-23, 694-банд

    Code text
    100 ўрингача бўлган заллар учун стол атрофидаги бир ўринга 1,3 — 2 m²; 100 дан кўп ва 150 ўрингача бўлган залларда пюпитр (китоб қўйиш мосламаси) бўлмаган столда бир ўринга 1-1,1 m², пюпитр (китоб қўйиш мосламаси) бўлган столда бир ўринга 1,25 m²; 150 ўриндан кўп залларда пюпитр (китоб қўйиш мосламаси) бўлмаган столда бир ўринга 0,9-1,0 m².
  8. Where there are 200 or more employees, a medical post and canteens must be provided.

    ШНҚ 2.08.02-23, 697-банд

    Code text
    Ходимлар сони 200 ва ундан кўп бўлганда тиббиёт пункти ва ошхоналар лойиҳаланиши керак.
  9. Where there are more than 200 employees, canteen capacity is designed for 20–30% of the staff; in buildings with fewer than 200 employees a snack bar is provided.

    ШНҚ 2.08.04-22, 75-банд

    Code text
    Ошхоналарнинг сиғими 200 ходимдан ортиқ кишига ҳисобланиб, хизматчиларнинг 20–30 фоиз учун мўлжалланиши керак. Ошхоналарни лойиҳалаштириш ШНҚ 2.08.02-23 га мувофиқ амалга оширилиши керак. Ходимлар сони 200 дан кам бўлган биноларда буфет лойиҳаланиши лозим.
  10. The width of internal corridors (other than recreation corridors) must be at least 1.8 m.

    ШНҚ 2.08.02-23, 28-банд

    Code text
    Ички йўлаклар (рекреация учун йўлаклар бундан мустасно) кенглиги 1,8 m дан кам бўлмаслиги лозим.
  11. In administrative buildings, corridors must be at least 1.5 m wide; corridors in the entrance zone for wheelchair users must be at least 1.8 m wide (1.6 m where this is not possible).

    ШНҚ 2.08.04-22, 16-банд

    Code text
    бунда йўлакларнинг эни 1,5 m дан кам бўлмаслиги лозим. Ўриндиқли аравачадан фойдаланадиган ногиронлиги бўлган шахслар учун кириш зонасидаги йўлаклар эни 1,8 m дан кам бўлмаслиги керак. Йўлаклар энини 1,8 m қилиб лойиҳалаш имкони бўлмаган ҳолда уларнинг энини 1,6 m бўлишига йўл қўйилади.
  12. The floor level at the building entrance must be at least 0.15 m above pavement level (a lower level is permitted if special measures against rainwater are taken).

    ШНҚ 2.08.02-23, 33-банд

    Code text
    Бинога кириш жойидаги пол сатҳи тротуар сатҳидан камида 0,15 m баланд бўлиши керак. Бинога кириш жойидаги пол сатҳини хоналарга ёғингарчилик сувлари оқиб киришини бартараф этувчи махсус чора-тадбирлар кўрилганда, тротуарнинг сатҳидан паст қилиб лойиҳалашга йўл қўйилади.
  13. The number of passenger lifts is determined by calculation, but must be at least two; the car depth of one lift must be at least 2,100 mm.

    ШНҚ 2.08.02-23, 131-банд

    Code text
    Йўловчи лифтларнинг сони ҳисоблаш орқали аниқланиши, бироқ уларнинг сони иккитадан кам бўлмаслиги зарур. Бинодаги битта йўловчи (ёки юк ташувчи) лифт кабинасининг бўйлама ўлчами 2100 mm дан кам бўлмаслиги керак.
  14. The distance from the door of the most remote room to the passenger lift door must not exceed 60 m.

    ШНҚ 2.08.02-23, 133-банд

    Code text
    Энг узоқ жойлашган хона эшиги олдидан йўловчи лифти эшигигача оралиқ масофа 60 m дан ошиб кетмаслиги зарур.
  15. Lift lobby width: with lifts on one side, not less than 1.3 times the smallest car depth; with lifts on both sides, not less than 2 times; in front of lifts with a car depth of 2,100 mm or more — at least 2.5 m.

    ШНҚ 2.08.02-23, 135-банд

    Code text
    лифт кабинаси энг кичик бўйлама узунлигининг 1,3 бараваридан кам бўлмаслиги (лифтлар бир томонлама жойлашганда); лифт кабинаси энг кичик бўйлама ўлчамининг 2 бараваридан кам бўлмаслиги (лифтлар икки томонлама жойлашганда); бўйлама ўлчами 2100 mm ва ундан катта бўлган лифтлар олдидаги холлнинг кенглиги 2,5 m дан кам бўлмаслиги.
  16. The width of a stair flight must not be less than the width of the exit onto the stairwell; in buildings occupied by more than 100 people — 1.35 m.

    ШНҚ 2.08.02-23, 24-банд

    Code text
    Зинапоя маршининг кенглиги зинапоя катагига чиқиш жойи кенглигидан кичик бўлмаслиги, ва унинг кенглиги қуйидагича бўлиши зарур: 1,35 m (Ф1 синфдаги биноларда, 100 нафардан ортиқ одамлар бўладиган биноларда, маданият ва аҳоли дам олиш марказлари, кинотеатр биноларида);
  17. Barriers must be installed along the roof perimeter of public buildings more than 10 m high; the barrier height must be at least 0.6 m.

    ШНҚ 2.03.10-24, 68-банд

    Code text
    Қаватлиги 3 ва ундан юқори қаватли турар жой объектлари, баландлиги 10 m дан ортиқ жамоат ва ишлаб чиқариш бинолари томларининг периметри бўйлаб тўсиқлар ўрнатилиши лозим. Тўсиқнинг баландлиги 0,6 m дан кам бўлмаслиги керак.

Fire safety and evacuation

  1. Fire and rescue vehicle access along both long sides of the building must be provided to class F4.3 (office) buildings 18 m high or more.

    ШНҚ 2.07.01-23, 666-банд

    Code text
    бинонинг иккала узун томонидан — баландлиги 28 m ва ундан юқори бўлган Ф1.3 синфига мансуб биноларга; баландлиги 18 m ёки ундан юқори бўлган Ф1.2, Ф2.1, Ф2.2, Ф3, Ф4.2, Ф4.3, Ф4,4 синфларига мансуб биноларга;
  2. Width of the access road for fire and rescue equipment: building height up to 13.0 m — 3.5 m; from 13.0 m to 46.0 m — 4.2 m; over 46 m — 6.0 m.

    ШНҚ 2.07.01-23, 667-банд

    Code text
    Ёнғин-қутқарув техникалари ўтиш йўллари кенглиги бино (иншоот)ларнинг баландлигидан келиб чиқиб, қуйидагилардан кам бўлмаслиги керак: биноларнинг баландлиги 13,0 m гача бўлганда — 3,5 m; биноларнинг баландлиги 13,0 m дан 46,0 m гача бўлганда — 4,2 m; биноларнинг баландлиги 46 m дан ортиқ бўлганда — 6,0 m.
  3. Distance from the inner edge of the fire and rescue vehicle access to the external wall of F1–F4 buildings: 5–8 m for buildings less than 28 m high, 8–10 m for buildings over 28 m high.

    ШНҚ 2.07.01-23, 675-банд

    Code text
    Ёнғин-қутқарув автомобили келиш жойининг ички қисмидан функционал ёнғин хавфи бўйича Ф1 — Ф4 синфларига мансуб биноларнинг ташқи деворлари ёки бошқа ўраб турган конструкцияларигача масофалар қуйидагилардан кам бўлмаслиги керак: баландлиги 28 m дан паст бўлган бинолар учун — 5 — 8 m; баландлиги 28 m дан ортиқ бўлган бинолар учун — 8 — 10 m.
  4. Rows of trees, fences, overhead power lines and other structures that obstruct the operation of aerial ladders and aerial platforms are not permitted between the fire and rescue vehicle access routes and the building.

    ШНҚ 2.07.01-23, 676-банд

    Code text
    Ёнғин-қутқарув автомобилларининг келиш жойлари билан бинолар орасидаги ҳудудларда ёнғин-қутқарув автонарвонлари ва автокўтаргичлари ишлашига тўсқинлик қилувчи қатор дарахтларни экиш, тўсиқлар (уй олди боғлари учун тўсиқлар бундан мустасно), ҳаво электр узатиш линиялари ва бошқа конструкцияларни ўрнатишга йўл қўйилмайди.
  5. Minimum fire separation distance between F1–F4 buildings: both buildings of degree I–III, class C0 — 6 m; adjacent building of degree II–III, class C1 — 8 m.

    ШНҚ 2.07.01-23, 56-жадвал

    Code text
    Ф1-Ф4 синфларига биноларнинг оловбардошлик даражаси ва конструктив ёнғин хавфи синфлари асосида минимал масофалар, m | I, II, III C0 | II, III C1 | Ф1-Ф4 синфларига мансуб бинолар | I, II, III | С0 | 6 | 8
  6. Storeys of class F4 buildings (offices belong to this class) must have at least two evacuation exits.

    ШНҚ 2.01.02-04, 5.13-банд

    Code text
    Қаватлари камида икки эвакуация чиқиш жойларига эга бўлиши керак: - Ф1.1; Ф1.2; Ф2.1; Ф2.2; ФЗ; Ф4. синфга мансуб бинолар;
  7. Evacuation exits must be at least 1.9 m high; width: at least 1.2 m where more than 50 people are evacuated from rooms and buildings of other classes (except F1.3), otherwise at least 0.8 m.

    ШНҚ 2.01.02-04, 5.16-банд

    Code text
    Эвакуация чиқиш жойлари баландлиги 1.9 м дан, эни эса кам бўлмаслиги керак: - 1.2 м дан - Ф1.1 синфга мансуб хонадан эвакуация қилинадиганлар сони 15 кишидан ортиқ бўлганда, бошқа вазифавий ёнғинга хавфли хона ва бинолардан, Ф1.3 синфга мансублари 50 кишидан ортиқ бўлганда бундан мустасно. - 0.8м дан – бўлган ҳамма ҳолларда.
  8. In buildings over 28 m high, smoke-free stairwells are as a rule of type Н1; in class F4 buildings, no more than 50% of the stairwells may be of type Н2 or Н3.

    ШНҚ 2.01.02-04, 5.40-банд

    Code text
    Баландлиги 28 м дан ортиқроқ биноларда, ҳамда Ф5 синфга мансуб, А ва Б тоифадаги биноларда, одатда Н1 турдаги, тутун қопламайдиган зина катаклари назарда тутилиши керак. Йўл қўйилади: - Ф 1.1, Ф 1.2 ,Ф 2, Ф 3 ва Ф 4 синфларга мансуб, йўлакли турли 50% ортиқ бўлмаган Н2 ёки Н3 турдаги зина катакларини назарда тутишга
  9. Distance from the door of the most remote room to the stairwell entrance (flow density up to 2 persons/m²): in a degree I–III building — 60 m for rooms located between stairwells, 30 m for rooms opening onto a dead-end corridor.

    ШНҚ 2.08.02-23, 7-жадвал

    Code text
    Эвакуация пайтида одамлар оқимининг зичлиги*, киши/m² | 2 гача | I-III | А. Зинапоя катаклари ёки ташқарига чиқиш жойлари орасида жойлашган хоналарда эвакуация қилишда | 60 40 | Б. Боши берк йўлакка ёки холлга чиқадиган хоналардан эвакуация қилишда | 30 20
  10. Corridors must be subdivided by partitions with self-closing doors located no more than 60 m from each other and from the end of the corridor.

    ШНҚ 2.08.02-23, 31-банд

    Code text
    Йўлаклар (коридор) ўзи ёпилувчан эшиклари бўлган пардадеворлар билан ажратилиши, бунда улар бир-биридан ва йўлак (коридор) охиридан 60 m дан узоқ бўлмаган масофада жойлаштирилиши лозим.
  11. Public buildings of fire resistance degree I and II (C0): up to 16 storeys; in a 3–5-storey building, the floor area between fire walls is up to 5,000 m² for degree I and up to 4,000 m² for degree II.

    ШНҚ 2.08.02-23, 2-жадвал

    Code text
    Қаватларнинг юқори чегаравий сони | Ёнғинга қарши деворлар орасидаги қаватнинг йўл қўйиладиган майдони, m² | 3 — 5 | I II II III III IV IV IV | CO CO C1 CO C1 CO C1 C2, C3 | 16 16 9 5 4 2 2 2 | 5000 4000 2000 1200 800 - - -
  12. In buildings over 28 m high, one of the lifts must be designed to transport firefighting units.

    ШНҚ 2.08.02-23, 132-банд

    Code text
    Баландлиги 28 m дан юқори бўлган биноларда лифтлардан бири ёнғин ўчирувчи бўлинмани ташиш учун мўлжалланган бўлиши керак.
  13. All public buildings and structures must be equipped with an automatic fire suppression system.

    ШНҚ 2.08.02-23, 29-илова, 8-банд

    Code text
    Барча жамоат бинолари ва иншоотлари АЁЎҚ билан жиҳозланиши керак.

Accessibility

  1. Car parks for vehicles of people with disabilities must be located no more than 200 m from the building entrance and be marked with special signs.

    ШНҚ 2.07.02-24, 198-банд

    Code text
    Ногиронлиги бўлган шахсларни ташувчи махсус транспортлар ҳамда уларнинг шахсий автотранспорти учун автотураргоҳлар бино ёки иншоотнинг кириш қисмига яқин 200 m дан узоқ бўлмаган масофада бўлиши ва махсус белгилар ўрнатилиши лозим.
  2. A dedicated parking space for a vehicle of a person with disabilities must measure at least 3.6 × 6 m.

    ШНҚ 2.07.02-24, 200-банд

    Code text
    Ногиронлиги бўлган шахсларнинг транспорт воситаси учун ихтисослаштирилган тўхташ жойининг ўлчамлари 3,6 х 6 m дан кам бўлишига йўл қўйилмайди.
  3. In car parks in front of public buildings, ten per cent of the total number of spaces must be allocated to vehicles of people with disabilities.

    ШНҚ 2.07.02-24, 203-банд

    Code text
    Жамоат бинолари олдидаги автомобиль тўхташ жойларидаги ўринларнинг умумий сонидан ўн фоизи ногиронлиги бўлган шахсларнинг автомобиллари учун ажратилиши керак.
  4. In car parks, at least 5% of parking spaces (but no fewer than one space) must be allocated to vehicles of people with disabilities.

    ШНҚ 2.07.01-23, 411-банд

    Code text
    Автотураргоҳларда машина жойларининг камида 5 фоизи (лекин битта жойдан кам бўлмаган ҳолда) ногиронлиги бўлган шахсларнинг автомобиллари учун ажратилиши керак.
  5. Ramps for wheelchair users must be at least 1.0 m wide; the rise of each flight must not exceed 0.8 m, with a longitudinal gradient of 1:12.5 and a cross fall of 1:50.

    ШНҚ 2.07.02-24, 42-банд

    Code text
    Ўриндиқли аравачадан фойдаланадиган ногиронлиги бўлган шахслар ҳаракатланиши учун пандуснинг кенглиги 1,0 m дан кам бўлмаслиги керак. Пандус ҳар бир маршининг кўтарилиш баландлиги 0,8 m дан ошмаслиги, бунда пандуснинг бўйлама қиялиги 1:12,5, кўндаланг нишаблиги эса 1:50 нисбатда бўлиши лозим.
  6. A transparent, lightweight (unheated) draught lobby is provided in front of the building entrance doors: width at least 1.6 m, length at least 2.2 m; for a wheelchair, the entry area outside the draught lobby is at least 1.4×2.0 m.

    ШНҚ 2.07.02-24, 49-банд

    Code text
    Тамбурнинг эни камида 1,6 m ва узунлиги камида 2,2 m бўлиши керак. Ўриндиқли аравачадан фойдаланадиган ногиронлиги бўлган шахслар учун тамбурнинг кириш жойи етарли ўлчамларга (ташқарида камида 1,4х2,0 m) эга бўлиши,
  7. A room in which a person with disabilities using a wheelchair works must have an area of at least 12 m².

    ШНҚ 2.07.02-24, 119-банд

    Code text
    Ўриндиқли аравачадан фойдаланадиган ногиронлиги бўлган шахслар иш фаолиятини олиб борадиган хонанинг майдони камида 12 m² бўлиши керак.
  8. In buildings where wheelchair users and visually impaired people work, toilet cubicles must be provided on every floor, no more than 50 m from the workplace.

    ШНҚ 2.07.02-24, 152-банд

    Code text
    Ўриндиқли аравачадан фойдаланадиган ногиронлиги бўлган шахслар ва кўришда нуқсони бўлган шахслар фаолият юритадиган биноларда ҳожатхона кабиналари ҳар бир қаватда бўлиши ҳамда иш жойидан 50 m дан ошмаган масофада жойлаштирилиши керак.
  9. Footpaths in residential and public areas must be at least 2.0 m wide, and on streets with vehicular traffic at least 2.4 m wide.

    ШНҚ 2.07.02-24, 19-банд

    Code text
    Турар жойлар ва жамоат ҳудудларида пиёдалар йўлкасининг кенглиги 2,0 m дан, транспорт ҳаракатланадиган кўчаларда эса 2,4 m дан кам бўлмаслиги керак.
  10. Refuge area per person, taking into account all people with disabilities on the floor: wheelchair user — 2.40 m², wheelchair user with an attendant — 2.65 m², person with disabilities moving independently — 0.75 m².

    ШНҚ 2.07.02-24, 75-банд

    Code text
    ўриндиқли аравачадан фойдаланадиган ногиронлиги бўлган шахслар учун — 2,40 m²/киши; кузатувчи ҳамроҳлигида ҳаракатланувчи ўриндиқли аравачадан фойдаланадиган ногиронлиги бўлган шахслар учун — 2,65 m²/киши; мустақил ҳаракатланувчи ногиронлиги бўлган шахслар учун — 0,75 m²/киши;

Lighting and insolation

  1. Administrative buildings: in workrooms and offices, general artificial illuminance 300 lx (Г-0.8), UGR no more than 21, daylight factor with side daylighting 1.0%; in design halls and drawing offices — 500 lx, daylight factor 1.5%.

    ШНҚ 2.01.05-24, 9-илова, 1-жадвал

    Code text
    Умумий ёритишда | Бирлашган шинамсизлик кўрсаткичи UGR кўпида | Ён томондан ёритиш | 1. Ишчи хоналар ва офислар | Г-0,8 | 300 | 21 | 1,0 | 2. Лойиҳалаш заллари ва хоналари, конструкторлик, чизмачилик бюролари | 500 | 1,5
  2. Average horizontal illuminance of areas in front of buildings (building entrances and access routes, vehicle parking areas) — 10 lx; fire and service access roads — 5 lx.

    ШНҚ 2.01.05-24, 11-жадвал

    Code text
    Горизонтал текисликдаги ўртача ёритилганлик, lx | Шаҳар ҳудудига тегишли бўлмаган бино олди ҳудудлари (биноларга кириш ва ўтиш йўллари, транспорт тўхташ жойлари) | 10 | Ёнғиндан ҳимоя йўллари ва хўжалик эҳтиёжлари учун мўлжалланган йўллар | 5
  3. Average horizontal illuminance of open car parks and the aisles between them — 6 lx.

    ШНҚ 2.01.05-24, 21-жадвал

    Code text
    Ўртача горизонтал ёритилганлик, lx | Барча тоифадаги кўчалардаги очиқ автотураргоҳлар, шунингдек, кўчалардан ташқаридаги автотураргоҳлар орасидаги ўтиш жойлари | 6
  4. On north-facing façades the glazed area must be kept to a minimum, and the total area of all the building's window openings must not exceed 25% of the external wall area.

    ШНҚ 2.08.02-23, 160-банд

    Code text
    Биноларнинг шимолга қараган фасадларида ойна билан қопланадиган минимал майдон таъминланган бўлиши, бинодаги барча ёруғлик туширадиган туйнукларнинг жами майдони ташқи деворлар майдонининг 25 фоизидан ошмаслиги лозим.

Noise protection

  1. In office buildings, floors between workrooms and secretariats and separating them from common rooms: Rw 45 dB, Lnw 63 dB; walls and partitions between offices of different organisations: Rw 48 dB.

    ШНҚ 2.01.08-24, 9-илова, 1-жадвал

    Code text
    R_{w}, dB | L_{nw}, dB* | Маъмурий бинолар, офислар | 20. Ишчи хоналар, хоналар ва котибиятлар ўртасидаги ва бу хоналарни умум фойдаланадиган хоналардан (вестибюллар, холлар) ажратиб турувчи ёпмалар | 45 | 63 | 22. Турли ташкилотларнинг офислари ўртасидаги, турли ташкилотларнинг хоналари ўртасидаги деворлар ва тўсиқлар | 48
  2. In the dining halls of cafés, restaurants and canteens, the permissible equivalent sound level is 55 dBA and the maximum sound level 70 dBA.

    ШНҚ 2.01.08-24, 1-илова, 1-жадвал

    Code text
    Товуш даражалари, L_{А} ва товушни эквивалент даражалари, L_{Аэкв}., dBA | Товушни максимал даражалари, dBA | Кафе, ресторан, бар ва ошхоналарнинг овқатланиш залларида | 55 | 70

Building services

  1. Internal fire water supply: there is a separate row for 6–10-storey offices; in other public buildings of up to 10 storeys with a volume of 5,000–25,000 m³ — 1 jet, each at least 2.5 l/s; with a volume over 25,000 m³ — 2 jets.

    ШНҚ 2.04.01-22, 1-жадвал

    Code text
    Оқим | Ички ёнғинни ўчириш учун битта оқимга тўғри келадиган минимал сув сарфи, l/s | Офис бинолари: | баландлиги 6 дан 10 қаватгача ва ҳажми 25 000 куб метргача; | 2-позицияда кўрсатилмаган ётоқхоналар ва жамоат бинолари: | қаватлар сони 10 тагача ва ҳажми 5000 дан 25000 куб метргача; | 1 | 2.5 | шу баландликда, ҳажми 25 000 куб метрдан ортиқ бўлганда; | 2
  2. Cold season, workrooms up to 35 m²: air temperature 20 °C, air change rate at least 3.5 per hour, but no less than 60 m³/h per person; conference halls: 18 °C, at least 20 m³ per person.

    ШНҚ 2.08.02-23, 26-жадвал

    Code text
    Барча иқлимий ҳудудларда ҳавонинг ҳисобий ҳарорати, °С | 1 h да ҳавони алмаштириш карралиги, камида | Майдони 35 m² дан кам бўлган иш хоналари | 20 20-23 21-22 | 3,5 бироқ бир нафар кишига камида 60 m³/h тўғри келиши керак | Конференц-заллар, мажлис заллари | 18 18-21 19-20 | ҳисоблаш асосида, бироқ бир нафар кишига камида 20 m³ тўғри келиши керак
  3. Distance from underground utilities to the building foundations: water main and pressure sewer — 5 m, gravity sewer — 3 m, power cables of all voltages and communication cables — 0.6 m.

    ШНҚ 2.07.01-23, 8-жадвал

    Code text
    Ерости тармоқларидан масофа (ёруғликда), m | бино ва иншоотлар пойдевори | Сув қувури ва босимли канализация | 5 | Ўзи оқар канализация ва сув оқимлари | 3 | Барча кучланиш кабеллари ва алоқа кабеллари | 0,6
  4. Electrical loads of buildings of administrative bodies and design and engineering organisations up to 16 storeys high with more than 50 and up to 2,000 occupants fall into category II.

    ҚМҚ 2.04.17-19, 3.1-банд

    Code text
    Бошқариш муассасалари, лойиҳа ва конструкторлик ташкилотлари, илмий-тадқиқот институтлари бинолари: | - баландлиги 16 қаватгача бўлган биноларнинг, шунингдек ишловчилар миқдори 50 дан ортиқ ва 2000 кишигача бўлган биноларнинг электр қабулқилгичлари мажмуи | II;
  5. Refuse chutes must be provided in buildings of more than 5 storeys.

    ШНҚ 2.08.02-23, 145-банд

    Code text
    Чиқинди тушириш қувурлари 5 қаватдан юқори биноларда, кам қаватли 200 ва ундан ортиқ ўринли меҳмонхоналар ва санаторийларда лойиҳаланиши керак.

Schematic plans

Open-plan office (16 workstations)96.0 m²Reception14.4 m²Manager'soffice30.0 m²Meeting room(19 seats)39.6 m²Corridor72.0 m²Open-plan office (15 workstations)95.0 m²Lift lobby (2lifts)Toilets20.2 m²Equipmentstoreroom11.5 m²Open-plan office (7workstations)47.5 m²↑ North5 m
Part of an office block floor (30 × 15 m, sample) Workplace — at least 6 m² per employee (ШНҚ 2.08.02-23, clause 679): 16, 15 and 7 workstations in the open-plan offices; meeting room — 2 m² per seat (19 seats); reception — at least 12 m² per room (ШНҚ 2.08.04-22, clause 37); corridor width at least 1.8 m (ШНҚ 2.08.02-23, clause 28) — 2.4 m on the plan; lift lobby width ≥ 2.5 m (clause 135). Areas measured to wall centrelines (diagram).

Important

  • Table 29 of ШНҚ 2.07.01-23 gives, for administrative buildings, “1 parking space for every 10 m² of building area” (as in the source; the type of area — total floor area or footprint — is not specified). The model uses total floor area: 4,366 m² → 437 spaces. For this reason the model was reduced from 9 to 5 storeys and a 2-level underground car park was added (it is not shown in 3D — only the ramp, shafts and outline).
  • The scope of ШНҚ 2.08.04-22 “Administrative Buildings” (clause 2) covers buildings of government bodies, courts, the prosecutor's office, civil registry offices, apartment building management organisations, and design and research institutions. A private business centre is not listed in it — its clauses are cited as recommendations; the main code is ШНҚ 2.08.02-23 (offices — F4.3).
  • The share of spaces for people with disabilities differs between codes: ШНҚ 2.07.02-24 (clause 203) — 10% in front of public buildings, ШНҚ 2.07.01-23 (clause 411) — at least 5%. The model adopts the stricter requirement.
  • The distance from the red line to the office building, the distance from the waste area to the building and the number of bicycle spaces were not found in the codes on the site. The codes for underground car parks (ШНҚ 2.05.07-24) and external fire water supply (ШНҚ 2.04.02-19) are not on the site.
  • Table 7 of ШНҚ 2.08.02-23 (distance to the stairs) is corrupted in the text on the site (cells are mixed up) — no figures were taken from it; check the original.
  • The model and plans are a sample scheme for learning; they must not be used as a finished (standard) design.
  • The list is not complete — the most important numeric requirements were selected. In design, follow the full current text of the code and other codes as well (structures, utilities, etc.).